WET ALARM VALVE ASSEMBLY

MODEL CONNECTION TYPE OPERATING PRESSURE OPERATING TEMPERATURE DIMENSIONS APPLICATION AREA
WET ALARM
VALVE BODY
Grooved x Grooved
Grooved x Flanged
Flanged x Flanged
200psi-300psi 3”-8” Mechanical and electronical
alarm for use with check valves
or water flow detectors.
RETARD CHAMBER 200psi-300psi ¾”Bsp It is used in conjunction with wet pipe sprinkler
systems . It serves primarily as a hydraulic time
delay to prevent most false alarms associated
with fluctuating water supply pressures.
WATER MOTOR GONG 200psi-300psi ¾”Bsp Hydraulically operated indoor/outdoor alarm for
use with fire protection systems. Can be used in
conjunction with alarm check, dry pipe, deluge,
and preaction valves to sound a local high decibel
alarm.
PRESSURE SWITCH 200psi-300psi -40 °C ~ +71°C ½” Npt It can be used in conjunction with alarm check,
dry pipe, deluge, and preaction valves to detect
pressure shift and sounds an alarm.
  • Wet Pipe Sprinkler Systems are designed for heated buildings and areas susceptible to freezing( i.e. temperatures are about +4°C ).
  • If the sprinkler opens, the water flow opens the alarm valve disc and reaches the raetard chamber via alarm valve body. The retard chamber fills in seconds, first the pressure switch sounds the electrical alarm, after the water in the water motor gong sounds the mechanic alarm. UL LIST-FM certified.