DRY ALARM ASSEMBLY

MODEL CONNECTION TYPE OPERATING PRESSURE OPERATING TEMPERATURE DIMENSIONS APPLICATION AREA
DRY ALARM VALVE BODY Grooved x Grooved
Grooved x Flanged
Flanged x Flanged
175-250psi 2”-6”
RETARD CHAMBER 200psi-300psi 0 ¾”Bsp Minimizes false alarms caused by surges
or fluctuations in wet pipe sprinkler
systems
WATER MOTOR GONG 200psi-300psi ¾”Bsp Hydraulically operated indoor/outdoor alarm for
use with fire protection systems. It can be used
in conjunction with alarm check, dry pipe,
deluge, and preaction valves to sound a local high decibel alarm.
PRESSURE SWITCH 200psi-300psi -40 °C ~ +71°C ½” Npt It can be used in conjunction with alarm
check, dry pipe, deluge, and pre action valves
to detect pressure shift and sounds an alarm.
ACCELARATOR Threaded x Threaded 250psi ½” Npt Dry alarm valve
depressurizes accelerating
equipment.
AIR PRESSURE
MAINTENANCE
DEVICE
Threaded x Threaded 27-58psi ½” Npt Adjusts the pressure of the air coming from
compressor or ventilation installation and the
nitrogen.
  • The Dry Pipe Sprinkler System is a fire-protection system that utilizes water as an extinguishing agent, while the system piping from the Dry Pipe Valve to the automatic fusible sprinklers is filled with pressurized air or nitrogen. Dry pipe systems should be installed only where heat is not adequate to prevent freezing of water in all parts of, or in sections of, the system ( ambient temperature below +4°C). Air pressure must be lost from the system to trip the valve. Then water must travel through the piping network to the sprinklers. In the same time the pressure switch detects the falling air pressure and send the electrical alarm. UL LIST-FM certified.